Instructions For Use | Use Wavin approved press tools to make the pipe connection. Use proper tools for cutting and avoid burs. Use tools like bending pliers or bending springs to bend the pipe. Use only Wavin Tigris pipes with Wavin Tigris fittings for full warranty. Operate according to ISO 21003-2 conditions
|
Product Features | Technical specifications pipe:
- Roughness: 0,002 mm,
- Thermal expansion: 0,025 – 0,030 mm/m∙K,
- Thermal conductivity pipe: 0,4 W/ m∙K, Max .
- Operating pressure: 10 bar,
- Maximum Continous Operating temperature: 70 ˚C, Tmax / T mal function: 95 ˚C, 100 h,
- Composition: PE-RTII/Al/PE-RTII
- Pipe Outside diameter: 25 mm
- Wall thickness: 2.5 mm
Specifications insulation: -Thermal conductivity: 0,036 at 0°C/ 0,040 at 40°C/ 0,045 at 70°C
- Reaction to fire: Euroclass Bls1,d0
- Color: Red
- Thickness: 13 mm
- Outside diameter: Nominal 54 mm, max. 60 mm
|